Current Carrying Capacities for BS 7671:

Back to Low Voltage Cable Data Reference
Reference Installation Method Insulation type and number of conductors Armoured cables (underground) Armoured cables (methods C, E)
A1 PVC 3 PVC 2 XLPE 3 XLPE 2
A2 PVC 3 PVC 2 XLPE 3 XLPE 2
B1 PVC 3 PVC 2 XLPE 3 XLPE 2
B2 PVC 3 PVC 2 XLPE 3 XLPE 2
C PVC 3 PVC 2 XLPE 3 XLPE 2 XLPE 2 XLPE 3
D XLPE 3 XLPE 2
E PVC 3 PVC 2 XLPE 3 XLPE 2 XLPE 2 XLPE 3
F PVC 3 PVC 2 XLPE 3 XLPE 2
Size ([math]mm^{2}[/math]) Copper (Cu) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 10 10,5 11 12,5 13,5 14,5 15 17 18 19 21 22 16 19
1,5 13 13,5 14,5 16 17,5 18,5 19,5 22 23 24 26 27 21 25 27 23 29 25
2,5 17,5 18 20 22 24 25 27 30 31 33 36 39 28 33 36 31 39 33
4 23 24 26 29 32 34 36 40 42 45 49 52 36 43 49 42 52 44
6 29 31 34 37 41 43 46 51 54 58 63 68 44 53 62 53 66 56
10 39 42 46 51 57 60 63 70 75 80 86 91 58 71 85 73 90 78
16 52 56 61 69 76 80 85 94 100 107 115 121 75 91 110 94 115 99
25 68 73 80 90 96 101 112 119 127 138 149 161 96 116 146 124 152 131
35 83 89 99 111 119 126 139 148 158 172 185 200 115 139 180 154 188 162
50 99 108 119 134 144 153 170 180 192 211 225 242 135 164 219 187 228 197
70 125 136 151 170 184 196 218 232 246 272 289 310 167 203 279 238 291 251
95 150 164 182 207 223 238 266 282 298 333 352 377 197 239 338 289 354 304
120 172 188 210 239 259 276 309 328 346 388 410 437 223 271 392 335 410 353
150 196 216 240 262 299 319 357 379 395 450 473 504 251 306 451 386 472 406
185 223 245 273 296 341 364 409 434 450 516 542 575 281 343 515 441 539 463
240 261 286 321 346 403 430 484 514 538 613 641 679 324 395 607 520 636 546
300 298 328 367 394 464 497 559 593 621 711 741 783 365 446 698 599 732 628