Typical AC resistances for copper and aluminium insulated cables operating at 50Hz are based on values given in AS/NZS 3008.1.

Multicore Cables

Copper Conductors

Note that for tinned copper conductors, a scaling factor of 1.01 should be applied.

Size ([math]mm^{2}[/math]) AC Resistance ([math]\Omega[/math]\km) of Multicore Copper Cables
Circular Conductors Shaped Conductors
45oC 60oC 75oC 90oC 110oC 45oC 60oC 75oC 90oC
1 23.3 24.5 25.8 27 28.7 - - - -
1.5 14.9 15.7 16.5 17.3 18.4 - - - -
2.5 8.14 8.57 9.01 9.45 10 - - - -
4 5.06 5.33 5.61 5.88 6.24 - - - -
6 3.38 3.56 3.75 3.93 4.17 - - - -
10 2.01 2.12 2.23 2.33 2.48 - - - -
16 1.26 1.33 1.4 1.47 1.56 1.26 1.33 1.4 1.47
25 0.799 0.842 0.884 0.927 0.984 0.799 0.842 0.884 0.927
35 0.576 0.607 0.638 0.669 0.71 0.576 0.607 0.638 0.669
50 0.426 0.449 0.471 0.494 0.524 0.426 0.448 0.471 0.494
70 0.295 0.311 0.327 0.343 0.364 0.295 0.311 0.327 0.342
95 0.214 0.225 0.236 0.248 0.262 0.213 0.224 0.236 0.247
120 0.17 0.179 0.188 0.197 0.209 0.17 0.179 0.187 0.196
150 0.139 0.146 0.153 0.16 0.17 0.138 0.145 0.153 0.16
185 0.112 0.118 0.123 0.129 0.136 0.111 0.117 0.123 0.128
240 0.087 0.0912 0.0955 0.0998 0.105 0.0859 0.0902 0.0945 0.0988
300 0.0712 0.0745 0.0778 0.0812 0.0852 0.0698 0.0732 0.0766 0.08
400 0.058 0.0605 0.063 0.0656 0.0685 0.0563 0.0589 0.0615 0.0641
500 0.0486 0.0506 0.0525 0.0544 0.0565 0.0465 0.0485 0.0508 0.0526

Aluminium Conductors

Size ([math]mm^{2}[/math]) AC Resistance ([math]\Omega[/math]\km) of Multicore Aluminium Cables
Circular Conductors Shaped Conductors
45oC 60oC 75oC 90oC 45oC 60oC 75oC 90oC
16 2.1 2.22 2.33 2.45 2.1 2.22 2.33 2.45
25 1.32 1.39 1.47 1.54 1.32 1.39 1.47 1.54
35 0.956 1.01 1.06 1.11 0.956 1.01 1.06 1.11
50 0.706 0.745 0.784 0.822 0.706 0.745 0.783 0.822
70 0.488 0.515 0.542 0.569 0.488 0.515 0.542 0.568
95 0.353 0.373 0.392 0.411 0.353 0.372 0.392 0.411
120 0.28 0.295 0.31 0.325 0.279 0.295 0.31 0.325
150 0.228 0.241 0.253 0.265 0.228 0.24 0.253 0.265
185 0.182 0.192 0.202 0.212 0.182 0.192 0.202 0.211
240 0.14 0.148 0.155 0.162 0.139 0.147 0.154 0.162
300 0.113 0.119 0.125 0.131 0.112 0.118 0.124 0.13
400 0.0897 0.0943 0.0988 0.103 0.0886 0.0932 0.0978 0.102
500 0.073 0.0765 0.08 0.0835 0.0716 0.0752 0.0788 0.0824

Single Core Cables

Size ([math]mm^{2}[/math]) AC Resistance ([math]\Omega[/math]\km) of Single Core Cables
Aluminium Conductors Copper Conductors (1)
45oC 60oC 75oC 90oC 45oC 60oC 75oC 90oC 110oC
1 - - - - 23.3 24.5 25.8 27 28.7
1.5 - - - - 14.9 15.7 16.5 17.3 18.4
2.5 - - - - 8.14 8.57 9.01 9.45 10
4 - - - - 5.06 5.33 5.61 5.88 6.24
6 - - - - 3.38 3.56 3.75 3.93 4.17
10 - - - - 2.01 2.12 2.23 2.33 2.48
16 2.1 2.22 2.33 2.45 1.26 1.33 1.4 1.47 1.56
25 1.32 1.39 1.47 1.54 0.799 0.842 0.884 0.927 0.984
35 0.956 1.01 1.06 1.11 0.576 0.607 0.638 0.668 0.71
50 0.706 0.745 0.783 0.822 0.426 0.448 0.471 0.494 0.524
70 0.488 0.515 0.542 0.568 0.295 0.311 0.327 0.342 0.363
95 0.353 0.372 0.392 0.411 0.213 0.225 0.236 0.247 0.262
120 0.279 0.295 0.31 0.325 0.17 0.179 0.188 0.197 0.208
150 0.228 0.24 0.253 0.265 0.138 0.145 0.153 0.16 0.169
185 0.182 0.192 0.202 0.212 0.111 0.117 0.123 0.129 0.136
240 0.14 0.147 0.155 0.162 0.0862 0.0905 0.0948 0.0991 0.105
300 0.113 0.119 0.125 0.13 0.0703 0.0736 0.077 0.0803 0.0846
400 0.089 0.0936 0.0981 0.103 0.0569 0.0595 0.062 0.0646 0.0677
500 0.0709 0.0744 0.0779 0.0813 0.0467 0.0487 0.0506 0.0525 0.0547
630 0.0571 0.0597 0.0623 0.0649 0.0389 0.0404 0.0418 0.0432 0.0448

Note (1): for tinned copper conductors, a scaling factor of 1.01 should be applied.